查詢結果分析
來源資料
相關文獻
- 部分放電量測應用於油浸式變壓器實例介紹
- The Effect of Changes in the Internal Structure of a Schooling Fish on the Estimation Efficiency by Acoustic Methods
- The Use of Stationary Hydroacoustic Transducer to Study Diel and Seasonal Influences on the Distribution of Fish School in Water Adjacent to the Cooling Water Intake of Nuclear Power Plant III
- 超音波定位之變壓器部分放電檢測
- Cord Blood Myeloperoxidase in Preterm Infants with Periventricular Hyperechogenicity
- 變壓器繞組變形試驗之研究
- 電力變壓器部分放電定位算法研究
- Changes in Flow-Mediated Dilatation, Cytokines and Carotid Arterial Stenosis During Aggressive Atorvastatin Treatment in Normocholesterolemic Patients
- Transcatheter Closure of Atrial Septal Defect Guided by On-Line Transesophageal Echocardiography
- Pelvic Abscess after Ultrasound-Guided Aspiration of Endometrioma: A Case Report
頁籤選單縮合
題 名 | 部分放電量測應用於油浸式變壓器實例介紹=Introduction of Partial Discharge Measurement on an Oil-immersed Transformer |
---|---|
作 者 | 吳明學; 李長興; 邱敏彥; 黃智賢; | 書刊名 | 台電工程月刊 |
卷 期 | 741 2010.05[民99.05] |
頁 次 | 頁1-7 |
專 輯 | 部分放電與雷害防制技術.部分放電 |
分類號 | 448.2 |
關鍵詞 | 繞組變形; 部分放電; 介質 電力因數; 油浸式變壓器; 超音波; Winding deformation; Partial discharge; Dielectric power factor; Oil-immersed transformer; Acoustic emission; |
語 文 | 中文(Chinese) |
中文摘要 | 變壓器絕緣量測大致可分為離線量測及線上量測,基於運轉上經濟效益及測量結果準確性及可靠性的考量,以後者為目前相關的學術研究機構著重發展的方向。變壓器內部絕緣並非完美無瑕,送電後於絕緣脆弱處會有部分放電發生,此現象會隨著運轉時間 增長而逐漸增加,並以電磁場信號、聲音、絕緣油中分解出異常氣體…等方式顯現出來,因此而衍生出的測試方法有部分放電(檢測電磁場信號的變化)、超音波及油中氣體分析,其中又以部分放電測試法的反應速度最快、靈敏度最高,在本文會以98 年3 月於協和發電廠使用內置式UHF 感測器測量TSU-2 變壓器的實際案例作說明,並與離線的各種測法相互作比較,並介紹目前本公司己於數個發電廠新設變壓器所安裝的內置式UHF 感測器。 |
本系統中英文摘要資訊取自各篇刊載內容。