題 名 | 室內裝修與撒水設備對人命安全影響之研究=Research on the Influence for Life Safety between Interior Finishing and Sprinkler System |
---|---|
作 者 | 江好爵; 熊光華; 何明錦; | 書刊名 | 中央警察大學災害防救學報 |
卷 期 | 2 2001.06[民90.06] |
頁 次 | 頁41-73 |
分類號 | 441.574 |
關鍵詞 | 室內裝修; 撒水設備; 火災防護方法; 火災實驗; 實驗設計; Sprinkler system; Interior finishing; Fire protection measures; Experiment design; Fire experiment; |
語 文 | 中文(Chinese) |
中文摘要 | 以中央警察大學第五停車場之戶外兩間同尺寸(4m×4.5m×3m)鋼筋混凝土造(RC)室外全尺寸燃燒屋作為實驗場所,每個實驗燃燒屋分別依耐燃/易燃之室內裝修限制有/無撒水設備配置予以裝置及裝修後,施以一定之起火火源後,利用各種不同量測儀器量取數據,如溫度、氧氣濃度、CO濃度、C□濃度、煙層下煙高度,經實驗的結果得到下列結論: 1.撤水設備能在初期控制火勢使溫度於100℃以內(人命安全危險處:距地板面1.4m),而耐燃室內裝修僅六使溫度於700℃內。 2.氧氣濃度:有設置撒水設備對□濃度的控制有很大的影響。 3. CO濃度:在設置撒水設備對CO濃度的控制有很大的影響。 4. C□濃度:有設置撒水設備對C□濃度的控制有很大的影響。 |
英文摘要 | Fire experiments were conducted in two full-scale R.C. fire rooms (4m×4.5m×3m) located in Central Police University that are assumed to be the rooms of commerce or office building under the various interior finishing materials, sprinkler systems. Concentrations of oxygen, carbon monoxide and carbon dioxide, smoke layer, and temperature were measured. The main purpose of this study is to investigate the influence for life safety between interior finishing (passive fire protection measures) and sprinkler system (active fire protection measures). The partial results of the experiments of this study can be summarized as followings: (1) The sprinkler system can control the room temperature within 100℃ (under 1.4m height) at very early at stage while the fire resistance interior can control the room temperature within 700℃. (2) The oxygen concentrations were strongly affected by the sprinklers' actuation. (3) The concentrations of carbon monoxide and carbon dioxide were strongly affected by the sprinklers' actuation. (4) The descending rates of smoke layer were strongly affected by the sprinklers' actuation. |